Winter not only we need to keep warm, as refrigeration people, we also have to "take care of and maintain" our refrigeration equipment, especially in the cold north, should pay attention to the central air conditioning should also do cold measures, especially shopping malls, manufacturing enterprises, hotels and other large field of commercial central air conditioning need more anti-freezing, so how to anti-freezing, anti-freezing what are the measures?
First, the main engine of anti-freezing
Close the inlet and outlet valves of the main engine condenser or evaporator, open the water drain valve and air drain valve, and then use compressed air to blow the remaining water.
Two, the anti-freezing water pump
Close the inlet and outlet valve of the coolant pump, open the drainage valve and vent valve of the pump, and exhaust the water. Open the lowest point valve of the cooling water system, discharge the cooling water, and open the water pump discharge valve. After the system water is discharged, in order to prevent rainwater from entering through the cooling tower, close the water main valve of the cooling tower and open the sewage valve of the collecting water tray of the cooling tower, so that rainwater can be discharged from the sewage valve in time.
Antifreezing of water refill pipe of cooling tower
Generally, the water refill pipe of the cooling tower is exposed to the outdoors. Most designers adopt the insulation method to prevent freezing, but in the actual use process, freezing damage often occurs even if the insulation is used.
In order to solve this problem, when the cooling tower water refill pipe is connected from the room, a valve is added, and a water discharge valve is added at the lowest point of the water refill pipe. When winter comes, the indoor valve is closed, and the lowest point of the water valve is opened, the outdoor water inside the pipe, so that the pipe does not need to be insulated and will not be frozen crack.
Four, the expansion tank of anti-freezing
The expansion tank is generally located in the equipment room on the roof or the top floor. Although there is thermal insulation on the surface of the expansion tank, and there is a circulation tube, but in actual use, the circulation tube can play a circulatory role very little. That is, in winter, there is water in the expansion tank in a low temperature environment for a long time, although it is insulated, it will still be frozen.
In order to solve this problem, a DN20 interface can be set up in the air conditioning water supply main pipe during construction, and a valve can be properly opened to ensure that the water in the tank is circulated. If the air conditioner is not used at night, the valve can be fully opened before the water pump stops, so that the water temperature in the expansion tank will rise, and the expansion tank will not freeze for a long time after the pump stops.
Five, fresh air system anti-freezing
The role of the fresh air unit is to send the outdoor fresh air into the room after treatment. In winter, the fresh air unit heats the outdoor cold air, that is, the fresh air unit table cooler directly contacts with the outside cold air. In order to prevent the table cooler from being frozen when the heating is stopped, the electric multi-leaf regulating valve should be added at the entrance of the fresh air, and the fresh air unit linkage. When the fresh air unit is running, the air valve is open, and when the fresh air organ is closed, the air valve is closed, which can prevent the fresh air unit and the refrigerant water pump from running, and the outdoor cold air will directly cool the water in the table cooler, so that the water is frozen and the table cooler is frozen.
Six, add antifreeze
In winter, the unit is not convenient to drain water and empty, and it is possible to cut off water and power. The equipment heating must be added with antifreeze, and it must be selected according to the local minimum temperature as an important parameter of antifreeze.
The main component of antifreeze is glycol, antifreeze from the fill tank, the water system after the discharge of frozen water, injected antifreeze stock solution, not enough to inject frozen water, and then open the pump to make antifreeze and water fully integrated, by the way, the water system of all air discharge, water system can not have air, air will make air conditioning equipment reported water switch protection, Also easy to form cavitation.
Vii. All freezing pipes are insulated
The main purpose of chilled water pipe insulation is to prevent condensation on the outside of the pipe. Another function is to prevent the water in the pipe from freezing. The thickness of the insulation layer is generally above 20mm.
In addition, but also on the outside of the water pipe around the electric tracing tropical, as long as the tracing tropical power supply, it can continue to heat the pipeline, the water temperature in the pipeline is above 10℃, coupled with the heat preservation outside the tropical, there will be no ice caused by the water heater water shortage protection. With the tropics to choose a temperature limit, keep a certain temperature.